Specifications | Range | Best Accuracy | |
Model | UT595 | ||
Insulation resistance (Ω) | Output voltage | 250V/500V/1000V | ±10% |
250V | 0.05MΩ~250MΩ | ±(5%+5) | |
500V | 0.05MΩ~500MΩ | ||
1000V | 0.05MΩ~1000MΩ | ||
Short-circuit current | <2mA | ||
Low-resistance continuity test | Range | 0.00Ω~199Ω | ±(2%+5) |
Test current | 0.00~2Ω: >200mA | √ | |
Line impedance (Ω) | Range | 0.01Ω~2000Ω | ±(5%+5) |
Operating voltage (Frequency) | 195V~440V (45Hz~65Hz) | √ | |
Test current | 20A | √ | |
PFC test | 0kA~26kA | √ | |
Loop impedance (Ω) | Range | 0.01Ω~2000Ω | ±(5%+5) |
Operating voltage (Frequency) | 195V~253V (45Hz~65Hz) | √ | |
Test current | 20A | √ | |
PFC test | 0kA~26kA | √ | |
Non-trip loop impedance (Ω) | Range | 1.00Ω~2000Ω | ±(5%+5) |
Operating voltage (Frequency) | 195V~253V (45Hz~65Hz) | √ | |
Test current | 15mA | √ | |
PFC test | 0kA~26kA | √ | |
RCD test | Operating voltage (Frequency) | 195V~253V (45Hz~65Hz) | √ |
Test current | 10mA/30mA/100mA/300mA/500mA | ±10% | |
Trip time | ×1/2 *I△n Range: 0ms~2000ms | ±(5%+5) | |
×1 *I△n Range: 0ms~300ms | |||
×1 *I△n Range: 0ms~500ms (Select count down) | |||
×2 *I△n Range: 0ms~150ms | ±(5%+5) | ||
×2 *I△n Range: 0ms~200ms (Select count down) | ±(5%+5) | ||
×5 *I△n Range: 0ms~40ms | ±(5%+5) | ||
Phase sequence test | Operating voltage (Frequency) | 100V~440V (45Hz~65Hz) | √ |
Display | Phase sequence: L1→ L2→ L3, forward rotation; L1→ L3→ L2 reverse rotation | √ | |
Ramp RCD test | Test current | 10mA/30mA/100mA/300mA/500mA | ±10% |
AC voltage (V) | Range | 0V~440V | ±(5%+2) |
Frequency response | 45Hz~60Hz | √ | |
Resolution | 1V | √ | |
Features | |||
Display count | 9999 | ||
Auto power off | √ | ||
Low battery indication | √ | ||
Data storage | √ | ||
LCD backlight | √ | ||
Auto half-wave test | √ | ||
RCD count down test | 30s | √ | |
RCD half-wave test | √ | ||
Phase conversion (RCD) | 0° and 180° | √ | |
General Characteristics | |||
Power | 1.5V battery (5#) × 6 | ||
LCD size | 125mm × 37mm | ||
Product color | Red and grey | ||
Product net weight | 1000g | ||
Product size | 210mm × 175mm × 90 mm | ||
Standard accessories | Battery, test leads (red×1, green×1, black×1), special power test lead, remote-control test lead | ||
Standard individual packing | Gift box, manual, tool box | ||
Standard quantity per carton | 4pcs | ||
Standard carton measurement | 510mm×330mm×300mm | ||
Standard carton gross weight | 15kg |
1. Where is your company?
we are located in Guangzhou, the capital city of Guangdong Province, near to Shenzhen, Foshan & Hong Kong, very convenient for shipping.
2. How about the MOQ?
1 unit is ok.
3. Shipping methods and lead time?
By Express: 5-7 working days to your door (DHL, UPS, TNT, FedEx...).
By Air: 7-10 working days to your airport.
By Sea: Pls advise your port of destination, the exact days will be confirmed by our forwarders, and the following lead time is for your reference.Europe and America (25 - 35 days), Asia (3-7 days), Australia ( 16-23 days).
4. What is the term of Payment?
T/T, L/C,Western Union, Paypal;
30% T/T in advance,70% before delivery.
5. What are your main products?
Compressor;
Refrigeration gas;
Refrigeration spare parts ;
Cold room panels and equipments .
6. Packaging & Shipping:
Packing: wooden pallet, wooden case or with outer carton, or as per customers' specific requirements.